What should I pay attention to when replacing the UPS battery?
1. Pay attention to personal safety and equipment safety. You must understand the site conditions before construction, and avoid affecting the normal operation of UPS host and power distribution cabinets during construction;
2. In the process of carrying the battery, pay attention to avoid the collision and damage of the battery, be careful to handle it with care, and two people should operate it when carrying it;
3. Since the site space is relatively narrow, pay attention to keeping the passages unblocked, and at the same time pay attention to the environment around Party A to avoid affecting Party A's normal work;
4. Pay attention to the reverse connection of the positive and negative poles of the battery during operation, and the installer should not bring metal objects such as watches during construction to avoid short-circuiting and ignition;
5. Seal and isolate the smoke probes of the fire fighting system in the machine room to avoid accidents caused by the fire fighting system false alarms and jet fire extinguishing. At the same time, carbon dioxide fire extinguishers and other fire safety protection devices are placed in the construction site;
6. When the staff are not in the UPS battery room, they must do a good job of safety precautions to avoid unnecessary accidents; for the battery packaging, it is necessary to replace and disassemble as much as possible;
7. Pay attention to the installation space and installation light problems during the construction of the lower layer of the battery rack, and each step must be careful, serious, correct and standardized;
8. The battery voltage should be measured every time a set of batteries is installed. Make sure that the voltage of each set of batteries is the same before connecting them in parallel. It is forbidden to connect battery packs of different voltages in parallel; and place the replaced old batteries in the location specified by the user. Misplaced
9. When connecting the battery terminals, it should not be too tight or too loose. After installing a set, you must pull the battery terminals to check whether the connection is firm;
10. Keep in touch with the relevant person in charge of the user, and communicate and report to the relevant person in charge in time if there is any problem.
Zhengzhou Kanglida Electronic Power Supply Co., Ltd. was established in 2000, specializing in the development, production and sales of four series of 2V, 4V, 6V, 12V maintenance-free lead-acid batteries and electronic chargers. Products are widely used in anti-theft alarm systems, fire alarm systems, building intercom systems, elevator emergency evacuation systems, emergency lights, attendance machines, sprayers, electronic scales, children's electric motorcycles, cartoon inflatables, car washers, table turntables, parking locks, Flashing lights, traffic lights, DC screens, solar energy, wind energy, UPS, EPS and other backup power systems, if you choose a company, you must choose a company with guaranteed reputation and quality. This company has been operating for many years and has many years of experience. Experienced company, so if you have a need for this, you may wish to contact us, I believe it is a good choice.